Medium Voltage Covered Conductors are designed to enhance the reliability and safety of electricity distribution networks. These conductors have proven to be highly functional, durable, and dependable in overhead power distribution systems. They consist of a conductor covered with a protective insulating layer that helps prevent accidental contact with other covered conductors or grounded objects such as tree branches, thereby reducing faults and power interruptions. Medium Voltage Covered Conductors are available in voltage ratings ranging from 11kV to 33kV. The standards applicable to these conductors include EN 50397-1 and IS 398 Part IV.
Anti-Tracking Protection
The outer covering of MVCC is manufactured using specially formulated Anti-Tracking XLPE (Cross Linked Polyethylene) compound. This material is designed to resist electrical tracking, which can occur when moisture, dust, pollution, or contaminants on the conductor surface create a conductive path leading to insulation failure. Anti-tracking properties significantly improve the conductor’s resistance to surface leakage currents, enhancing operational safety and extending service life, especially in humid, coastal, industrial, and polluted environments.
Water Blocking Compound
MVCC conductors are also equipped with Water Blocking Compound or Water Swellable Materials to prevent the longitudinal ingress of moisture inside the conductor. In the event of damage to the outer covering, the water blocking system restricts the spread of moisture along the conductor length, protecting the conductor against corrosion, insulation deterioration, and electrical failures. This feature greatly improves the long-term reliability and durability of the distribution network, particularly in high rainfall and high humidity areas.
Technical Specifications
Layer: 3 Layers
| Technical Specification of 100 Sq.mm 11KV & 33KV Medium Voltage Covered Conductor (MVCC) | |||
|---|---|---|---|
| TEST DESCRIPTION | UNITS | SPECIFIED VALUE | |
| 1. Test on Conductor (All Aluminium Alloy) | |||
| 1.1 No. of Strands | Nos. | 7 | 7 |
| 1.2 Wire Diameter (Nom.) | mm | 4.26 | 4.26 |
| 1.3 Bare Conductor Diameter (Approx.) | mm | 12.78 | 12.78 |
| 1.4 Lay Ratio | 10 to 14 | 10 to 14 | |
| 1.5 Breaking Load of Individual Strands | kN | 4.18 (Min) | 4.18 (Min) |
| 1.6 Conductor Resistance @ 20 0C | Ohm/km | 0.339 | 0.339 |
| 2. Insulation | |||
| 2.1 Thickness of Semi-con | mm | 0.3 | 0.4 |
| 2.2 Thickness of Inner XLPE Insulation | mm | 1.2 | 2.43 |
| 2.3 Thickness of Outer Covering Insulation | mm | 1.1 | 1.2 |
| 2.4 Tensile Strength of XLPE Insulation | N/mm2 | 12.5 | 12.5 |
| 2.5 Elongation of XLPE Insulation | % | 200 | 200 |
| 2.6 Hot Set on 200±30C for 15 minutes | |||
| 2.6.1 Maximum Elongation under load | % | 175 (max.) | 175 (max.) |
| 2.6.2 Maximum Permanent Elongation after Cooling | % | 15 (max.) | 15 (max.) |
| 3. Overall Diameter | mm | 18 (Aprrox.) | 21 (Aprrox.) |
| Technical Specification of 55 Sq.mm 11KV & 33KV Medium Voltage Covered Conductor (MVCC) | |||
|---|---|---|---|
| TEST DESCRIPTION | UNITS | SPECIFIED VALUE | |
| 11KV | 33KV | ||
| 1. Test on Conductor (All Aluminium Alloy) | |||
| 1.1 No. of Strands | Nos. | 7 | 7 |
| 1.2 Wire Diameter (Nom.) | mm | 3.15 | 3.15 |
| 1.3 Bare Conductor Diameter (Approx.) | mm | 9.45 | 9.45 |
| 1.4 Lay Ratio | 10 to 14 | 10 to 14 | |
| 1.5 Breaking Load of Individual Strands | kN | 2.29 (Min) | 2.29 (Min) |
| 1.6 Conductor Resistance @ 20 0C | Ohm/km | 0.621 | 0.621 |
| 2. Insulation Tests | |||
| 2.1 Thickness of Semi-con | mm | 0.3 | 0.4 |
| 2.2 Thickness of Inner XLPE Insulation | mm | 1.2 | 2.43 |
| 2.3 Thickness of Outer Covering Insulation | mm | 1.1 | 1.2 |
| 2.4 Tensile Strength of XLPE Insulation | N/mm2 | 12.5 | 12.5 |
| 2.5 Elongation of XLPE Insulation | % | 200 | 200 |
| 2.6 Hot Set on 200±30C for 15 minutes | |||
| 2.6.1 Maximum Elongation under load | % | 175 (max.) | 175 (max.) |
| 2.6.2 Maximum Permanent Elongation after Cooling | % | 15 (max.) | 15 (max.) |
| 3. Overall Diameter | mm | 15 (Aprrox.) | 17.5 (Aprrox.) |