Rathi FR Cable stands as a symbol of excellence in Nepal’s house wiring industry, delivering a perfect balance of quality, safety, and affordability. Built with precision and high manufacturing standards, it is designed to provide reliable electrical performance while ensuring enhanced protection against fire risks. Recognized as one of the best options in the affordable segment, Rathi FR Normal Cable makes safe and durable wiring accessible to every household without compromising on excellence.
Trusted by professionals and homeowners alike, it continues to set the benchmark for dependable house wiring solutions across Nepal.
Technical Specifications
| S.N. | Test Description | Unit | Requirement (Type A) | Test Method |
|---|---|---|---|---|
| 1 | Insulation resistance constant (Min) | |||
| a) at 27∘C | MΩ⋅km | 36.7 | IS 10810, Part 43 | |
| b) at maximum rated temperature | MΩ⋅km | 0.037 | ||
| 2 | Without ageing | |||
| a) Tensile strength (Min) | N/mm2 | 12.5 | IS 10810, Part 7 | |
| b) Elongation at break (Min) | % | 150 | ||
| 3 | After ageing in air oven | |||
| a) Treatment (Temp ±2∘C / Duration) | °C / Days | 80∘C / 7 Days | IS 10810, Part 11 | |
| b) Tensile strength (Value Min / Variation Max) | N/mm2 / % | 12.5 / +20 | ||
| c) Elongation at break (Value Min / Variation Max) | % / % | 150 / ±20 | ||
| 4 | Loss of mass in air oven | |||
| Treatment (Temp ±2∘C / Duration) | °C / Days | 80∘C / 7 Days | IS 10810, Part 10 | |
| 5 | Hot deformation test | |||
| a) Test temperature (±2∘C) | °C | 80∘C | IS 10810, Part 15 | |
| b) Time under load (1st case / 2nd case) | Hours | 4 / 6 | ||
| c) Depth of indentation (Max) | % | 50 | ||
| 6 | Heat shock test | |||
| Treatment (Temp ±2∘C / Duration) | °C / Hours | 150∘C / 1 Hour | IS 10810, Part 14 | |
| 7 | Shrinkage test | |||
| Treatment (Temp ±2∘C / Duration) | °C / Mins | 150∘C / 15 Mins | IS 10810, Part 12 | |
| b) Shrinkage (Max) | % | 4 | ||